PowerSourcesHistorisches Archiv / Historical archive
Historical archive — product data, prices and company statements reflect the former website and are not current offers.

PowerSources / Archiv

Argo3TM UPS - On line double conversion UPS




Uninterruptible
power supply
On line double conversion
10-20KVA







    • 3-phase input/1-phase output.
    • On line Double conversion with transformer.

    • High frequency IGBT inverter.

    • Microprocessor control.
    • Self-diagnose.
    • Multilanguage LCD display allows a comprehensive UPS management (setting, measures).

    • Designed for any kind of application.
    • Wide input voltage range.
    • Sine-wave regulated output voltage.
    • Back-feed protection device.
    • Static and Service By-Pass.
    • Automatic and manual battery test.
    • Autonomy extension capability.
    • PRedundant parallel architecture (up to 6 units).
    • Low acoustic noise.
    • N° 2 RS232 serial ports, EPO and contacts port.
    • Remote display panel.
    • Economy Mode for energy saving.

    • CD Shutdown software, for most common Operating Systems.
    • SNMP capability.

Technical characteristics
SYSTEM 1-phase output MODELS
Nominal Capacity [KVA] 10 15 20
Input 3-phase + N
Remote signals Voltage free contacts
Remote command EPO
Communication RS232/C
Environment temperature 0 - 40° C
Humidity 95% (non condensing)
Cooling Forced air
Acoustic noise <54 dBA
Protection degree IP20
Efficiency > 90%
In compliance with Safety EN 50091-1-1 ,EMC EN 50091-2 Lev. B
Dimensions WxDxH [mm] 555x720x1200
Weight w/o battery [Kg.] 200 220 240
INPUT RECTIFIER
Nominal Voltage 400V 3-phase + N
Voltage range ± 20%
Frequency range [Hz] 45 ÷ 65 Hz
BATTERY
Type Sealed lead acid maintenance free
Battery voltage 384 Vdc
OUTPUT INVERTER
Power rating [KVA] 10 15 20
Active power [kW] 8 12 16
Phase number 1
Nominal voltage 220/230/240V
Crest Factor [Ipeak/Irms] 3:1
Wave shape Sinusoidal
Distortion with linear load 3%
Static stability ± 1%
Dynamic stability ± 5% in 10 ms
Frequency [Hz] 50 / 60 selectable
Overload 125/150% nominal current 10’ / 1’
BY-PASS
Nominal Voltage 230V
Admitted overload 200%
Transfer time 0 ms.
Nominal frequency [Hz] 50 / 60

    to Overview