Technical characteristics
| SYSTEM | 1-phase output MODELS | ||
| Nominal Capacity [KVA] | 10 | 15 | 20 |
| Input | 3-phase + N | ||
| Remote signals | Voltage free contacts | ||
| Remote command | EPO | ||
| Communication | RS232/C | ||
| Environment temperature | 0 - 40° C | ||
| Humidity | 95% (non condensing) | ||
| Cooling | Forced air | ||
| Acoustic noise | <54 dBA | ||
| Protection degree | IP20 | ||
| Efficiency | > 90% | ||
| In compliance with | Safety EN 50091-1-1 ,EMC EN 50091-2 Lev. B | ||
| Dimensions WxDxH [mm] | 555x720x1200 | ||
| Weight w/o battery [Kg.] | 200 | 220 | 240 |
| INPUT RECTIFIER | |||
| Nominal Voltage | 400V 3-phase + N | ||
| Voltage range | ± 20% | ||
| Frequency range [Hz] | 45 ÷ 65 Hz | ||
| BATTERY | |||
| Type | Sealed lead acid maintenance free | ||
| Battery voltage | 384 Vdc | ||
| OUTPUT INVERTER | |||
| Power rating [KVA] | 10 | 15 | 20 |
| Active power [kW] | 8 | 12 | 16 |
| Phase number | 1 | ||
| Nominal voltage | 220/230/240V | ||
| Crest Factor [Ipeak/Irms] | 3:1 | ||
| Wave shape | Sinusoidal | ||
| Distortion with linear load | 3% | ||
| Static stability | ± 1% | ||
| Dynamic stability | ± 5% in 10 ms | ||
| Frequency [Hz] | 50 / 60 selectable | ||
| Overload | 125/150% nominal current 10’ / 1’ | ||
| BY-PASS | |||
| Nominal Voltage | 230V | ||
| Admitted overload | 200% | ||
| Transfer time | 0 ms. | ||
| Nominal frequency [Hz] | 50 / 60 | ||