PowerSourcesHistorisches Archiv / Historical archive
Historisches Archiv — Produktdaten, Preise und Firmenangaben stammen aus dem früheren Auftritt und sind keine aktuellen Angebote.

PowerSources / Archiv

Argo TM USV - Doppelte-Online Sinuswellenumformungs USV




Uninterruptible
power supply
On line double conversion





    • 1-phase, 3-phase input/1-phase output.
    • Double conversion transformerless.
    • Compact size and light weight.

    • PFC circuit: high Power Factor and low harmonic distortion of input current (clean version).

    • Microprocessor control.
    • Self diagnose.
    • Multilanguage LCD display allows a comprehensive UPS management (setting, measures).

    • Designed for any kind of application.
    • Wide input voltage range.
    • Sine-wave regulated output voltage.
    • Efficiency increase.
    • Static and Service By-Pass.
    • Automatic and manual battery test.
    • Autonomy extension capability.
    • Redundant parallel architecture (up to 8 units).
    • Low acoustic noise, fans speed regulation.
    • N° 2 RS232 serial ports, EPO and contacts port.
    • Remote display panel.
    • Smart Active for energy saving.
    • Wheels equipped.
    • CD Shutdown software, for most common Operating Systems.
    • SNMP and modem capability.

Technical characteristics
SYSTEM 1-phase output MODELS
Nominal Capacity [KVA] 10 15 20
Input 1-phase or 3-phase
Remote signals Voltage free contacts
Remote commands EPO and by-pass
Communication 2 x RS232/C
Environment temperature 0 - 40° C
Humidity 95% (non condensing)
Cooling Forced air
Acoustic noise <56 dBA
Protection degree IP20
Efficiency > 92%
In compliance with Safety EN 50091-1-1 ,EMC EN 50091-2 Lev.A
Dimensions WxDxH [mm] 450x750x1200
Weight UPS +
standard battery [Kg]
90+90 95+135 110+135
INPUT RECTIFIER
Nominal voltage 220 - 230 - 240V 1-phase or 380 - 400 - 415V 3-phase + N
Voltage range ± 20%
Frequency range [Hz] 45 ÷ 65
Power Factor 0.95
Current distortion <7% 1-phase input, <27% 3-phase input (<9% clean version)
BATTERY
Type Sealed lead acid maintenance free
Number / V / Ah 32/12/7 48/12/7 48/12/12
Recharging time [h] 8
Autonomy full load [min.] 8 8 7
OUTPUT INVERTER
Power rating, input 1-phase [KVA] 10 15 20
Active power [kW] input 3-ph,1-ph. 8 12-10.5 16-12
Phase number 1
Nominal voltage 230V
Voltage adjusting range 200 ÷ 243V
Crest Factor [Ipeak/Irms] 3:1
Wave shape Sinusoidal
Distortion with linear load <2%
Static stability <1%
Dynamic stability <5% in 10 ms
Frequency [Hz] 50/60 selectable
Overload 125/150% nominal current 10’ / 1’
BY-PASS
Nominal voltage 230V
Phase number 1
Admitted voltage range ± 15% (selectable from ± 5% to ± 25%)
Nominal Frequency [Hz] 50 / 60
Admitted frequency range ± 2% (selectable from ± 1% to ± 5%)

    zur Übersicht