Technical Data:
| SYSTEM | MODEL | ||||||
| Nominal Capacity [KVA] | 200 | 250 | 300 | 400 | 500 | 600 | 800 |
| Input | 3-phase + N | ||||||
| Remote signals | Voltage free contacts | ||||||
| Remote command | EPO | ||||||
| Communication | RS232/C | ||||||
| Environment temperature | 0 - 40° C | ||||||
| Humidity | 90% (non condensing) at 20°C | ||||||
| Cooling | Forced air | ||||||
| Acoustic noise | <65 dBA | ||||||
| Protection degree | IP20 | ||||||
| Efficiency | > 93% | ||||||
| In compliance with | Safety EN-50091-1-1; EMC EN 50091-2 Lev.B | ||||||
| Weight w/o battery [Kg.] | 2100 | 2500 | 2800 | 3800 | 4200 | 4800 | 6000 |
| Dimensions WxDxH [mm] | 1800 x 1500 x 900 | 1800 x 2700 x 900 | |||||
| RECTIFIER INPUT | |||||||
| Nominal voltage | 380/400/415V 3-phase + N | ||||||
| Voltage range | ± 15% | ||||||
| Frequency range [Hz] | 50/60Hz +/- 5% | ||||||
| BATTERY | |||||||
| Type | Pb-Ca | ||||||
| Nominal voltage | 384Vdc | ||||||
| INVERTER OUTPUT | |||||||
| Power rating [KVA] | 200 | 250 | 300 | 400 | 500 | 600 | 800 |
| Active power [kW] | 160 | 200 | 240 | 320 | 400 | 480 | 640 |
| Phase number | 3 + N | ||||||
| Nominal voltage | 400V+N selectable 380/415 | ||||||
| Crest Factor (Ipeak/Irms) | 3:1 | ||||||
| Wave shape | Sinusoidal | ||||||
| Distortion with linear load | 3% | ||||||
| Static stability | ± 1% | ||||||
| Dynamic stability | ± 5% in 10 ms | ||||||
| Frequency [Hz] | 50/60 selectable | ||||||
| Overload | 125/150% nominal current 10’ / 1’ | ||||||
| BY-PASS | |||||||
| Nominal voltage | 400V + N | ||||||
| Admitted overload | 200% | ||||||
| Transfer time | 0 ms. | ||||||
| Nominal frequency [Hz] | 50 / 60 | ||||||